This low-voltage fire-resistant armoured cable from Liban Cables (Nexans Lebanon) features XLPE insulation with a fire-resistant barrier, steel wire armour, and a halogen-free low-smoke (LSOH) oversheath that limits toxic gas and smoke emission during fire.
Fire resistance is validated per IEC 60331-21 at 750°C for 90 minutes. All routine and type tests are performed per IEC 60502-1, with certificates issued by Liban Cables for all lengths supplied.
Insulation: XLPE with fire-resistant layer
Armour: steel wire armour (SWA)
Oversheath: halogen-free low-smoke (LSOH)
Standard: IEC 60502-1
Fire resistance: IEC 60331-21, 750°C, 90 minutes
Test voltage during fire: 500 V conductor-to-conductor; 300 V conductor-to-earth
DC resistance test: IEC 60228 and IEC 60502-1 para. 15.1 & 15.2
Voltage test: IEC 60502-1 para. 15.1 & 15.3
Insulation type test: IEC 60502-1 para. 16.5.2
Armour type test: IEC 60502-1 para. 16.7
Oversheath type test: IEC 60502-1 para. 16.5.3
Fire resistance: IEC 60331-21, 750°C, 90 minutes